Your are here: Home // Facilities // The Difference Between a Watt and a Volt Amp

The Difference Between a Watt and a Volt Amp

Usually seen when sizing unin­ter­rupt­able power sup­plies the Volt-Amp is often con­fused with Watts, they are not the same. The power require­ment of a piece of equip­ment is expressed in Watts of Volt Amps (VA), the most common example being of course the 100W light bulb.

A Watt is the actual or true power used or dis­sip­ated by the device

A Volt Amp is called the appar­ent power and is obtained by mul­tiply­ing the voltage by the current drawn by an altern­at­ing current device.

This is a small but sig­ni­fic­ant dif­fer­ence. The Watt rating is used for meas­ur­ing the power used and res­ult­ant heat. The VA is used for sizing calculations.

There are two types of load, res­ist­ive and reactive.

A light bulb is res­ist­ive but a com­puter or other elec­tronic device is reactive.

If we cal­cu­lated a the power used for a res­ist­ive light bulb oper­at­ing at 240volts and drawing 0.25ampere it is a matter of apply­ing a simple formula;

Power = Voltage x Current or 240 x 0.25

60 watts, the VA rating would be exactly the same.

Where the load is react­ive a power factor must be used. With react­ive loads a certain amount of power is absorbed by and sub­sequently released by the device. This power amount is called the react­ive power or the dif­fer­ence between appar­ent and true power.

In an example where a com­put­ing device has an imped­ance of 120 Ohms using Ohms law (current = voltage/resistance) 240/120 will produce a current figure of 2 amps.

Using the same formula as above to get power

Power = Voltage x Current or 240 x 2

The appar­ent power would then be 480VA

Since the load is elec­tronic, a power factor must be applied. Dif­fer­ent devices will have dif­fer­ent power factors; in this case the com­puter has a power factor of 0.9

Apply­ing the power factor to the appar­ent power results in a watt figure of 480 x 0.9 = 432 watts

This dif­fer­ence between the appar­ent power and true power is react­ive power, in this example 48 Volt Amps.

The vast major­ity of modern large com­puter devices now have very high power factors, usually close to 1 but smaller devices such as PC’s may be as low as 0.65

However, UPS devices do not have this high power factor. UPS devices are rated in VA with a stated power factor. The power factor is gen­er­ally accep­ted to be 0.6 for UPS devices designed to power PC’s and other small devices.

A typical 500VA UPS would deliver 300 Watts. To com­plic­ate things even further large UPS’s now have very high power factors, approach­ing 1

The UPS will have both maximum VA and Watt ratings that cannot be exceeded.

Careful thought needs to be applied to the correct sizing of UPS’s taking into account the nature of the load and design spe­cific­a­tions of the UPS itself in order to avoid errors. The safest approach is to keep the load at less than 60% of the VA rating of the UPS or seek expert advice